Cold air bypass within contained aisle data centres - experimental bypass measurements and calculations undertaken to estimate flows through, and power consumptions of servers.

Tatchell-Evans, Morgan and Kapur, Nik and Summers, Jonathan and Thompson, Harvey and Oldham, Dan (2016) Cold air bypass within contained aisle data centres - experimental bypass measurements and calculations undertaken to estimate flows through, and power consumptions of servers. University of Leeds. [Dataset] https://doi.org/10.5518/45

Dataset description

Underlying data relating to the paper "An experimental and theoretical investigation of the extent of bypass air within data centres employing aisle containment, and its impact on power consumption". The dataset includes raw experimental results, as well as calculations made on data obtained from other sources.

Additional information: A 36 month embargo applies to the file 'Measured bypass data'
Subjects: H000 - Engineering > H100 - General engineering > H140 - Mechanics > H141 - Fluid mechanics
H000 - Engineering > H300 - Mechanical engineering
Divisions: Faculty of Engineering and Physical Sciences > School of Mechanical Engineering